Battery Storage (BESS) Calculation Methods
Formulas and assumptions behind our battery degradation, state of health, thermal, and efficiency calculators.
Battery degradation (linear model)
This calculator uses a simplified linear degradation model — the same approach most battery warranties use for planning purposes — where capacity fades by a fixed percentage of original rated capacity each year. Remaining Capacity at Year N (%) = 100% − (annual degradation rate (%) × N), so a 2.5%/year rate retains 87.5% at year 5 and 75% at year 10. Remaining Capacity at Year N (MWh) = initial rated capacity (MWh) × (remaining % ÷ 100) — 350 MWh and 300 MWh respectively at 400 MWh initial capacity. Cumulative Capacity Lost (MWh) = initial rated capacity − remaining capacity at the final projection year, and Cumulative Capacity Lost (%) = 100% − remaining % at the final projection year (100 MWh and 25% by year 10 at the defaults). Years to Reach End-of-Life Threshold = (100% − end-of-life capacity threshold (%)) ÷ annual degradation rate (%), which is 8 years at an 80% threshold and 2.5%/year. The year-5 figure is always computed as a fixed mid-point reference regardless of projection period length. Real-world degradation is often front-loaded rather than perfectly linear; treat the linear output as a reasonable planning estimate, not a precise forecast. Data sources: typical utility-scale LFP degradation rates (2-3%/year for well-designed, moderately used systems); field data from a Southern Italy PV-integrated lithium-ion BESS (95.88% state of health after 3 years, 356 equivalent full cycles); industry-standard 80% end-of-life capacity threshold.
Battery state of health (SOH)
State of Health (SOH) is a percentage comparing a battery's currently measured usable capacity to its original rated (nameplate) capacity — the standard way to express how much a battery has degraded at a specific point in time, based on an actual measurement rather than a projection. SOH (%) = (measured current capacity (MWh) ÷ original rated capacity (MWh)) × 100, so 350 MWh measured against 400 MWh rated is 87.5%. Capacity Fade (%) = 100% − SOH and Capacity Fade (MWh) = rated − measured — 12.5% and 50 MWh at the defaults. Implied Average Annual Degradation Rate (%/year) = Capacity Fade (%) ÷ age in service (years), which works backward from the one measured reading to the average annual rate that would produce it: 12.5% over 5 years is 2.5%/year. Remaining Useful Life to End-of-Life Threshold (years) = (SOH (%) − end-of-life threshold (%)) ÷ implied rate — (87.5 − 80) ÷ 2.5 = 3.0 years — and is reported as 0 years when SOH is already at or below the threshold. The primary flag grades the SOH reading (excellent ≥90%, healthy 80-90%, below the 80% end-of-life threshold <80%); the secondary flag grades the implied rate against the 2-3%/year utility-scale LFP benchmark. Data sources: industry-standard 80% end-of-life threshold (warranties and project financial models); typical utility-scale LFP degradation benchmark (2-3%/year for well-designed, moderately used systems).
Battery thermal management (cooling load)
Every charge and discharge cycle has losses — the same losses measured by round-trip efficiency — and that lost energy becomes heat inside the battery system that must be actively removed. Daily Energy Discharged (MWh) = Daily Energy Charged (MWh) × (Round-Trip Efficiency (%) ÷ 100), so 400 MWh charged at 87% RTE is 348 MWh discharged. Heat Generated per Day (MWh) = Daily Energy Charged − Daily Energy Discharged — 52 MWh at the defaults. Cooling Energy Required per Day (MWh) = Heat Generated per Day ÷ Cooling System COP, where COP (Coefficient of Performance) is the units of heat removed per unit of electrical energy the cooling system consumes; at COP 3.0, rejecting 52 MWh of heat takes 17.33 MWh. Annual Cooling Energy Consumption (MWh/year) = Cooling Energy Required per Day × 365 — about 6,332 MWh/year. Annual Cooling Energy Cost ($/year) = Annual Cooling Energy Consumption × Electricity Price ($/MWh) — roughly $316,583/year at $50/MWh. Cooling Load as % of Daily Throughput = (Cooling Energy Required per Day ÷ Daily Energy Charged) × 100 — 4.33% at the defaults. Air cooling typically runs a COP of 2.5-3.5 in moderate climates, dropping to 1.8-2.2 in hot climates above 35°C ambient; liquid cooling typically runs 3.5-5.0 and holds up more consistently across climates. Data sources: air cooling COP ranges (2.5-3.5 moderate climate, 1.8-2.2 hot climate >35°C ambient); liquid cooling COP range (3.5-5.0); liquid cooling cycle-life extension (15-25% vs. air cooling); 10-year TCO reduction for liquid cooling ($80,000-120,000 for 2MWh+ systems); liquid cooling CAPEX premium (30-40% vs. air cooling); IEC 62619 thermal management standards compliance.
BESS round-trip efficiency
Round-trip efficiency (RTE) is the percentage of energy you get back out of a battery compared to what you put in — energy discharged divided by energy charged. It captures every loss in the system: cell chemistry losses (internal resistance), inverter/power conversion system losses (often 5-8% alone), auxiliary loads like HVAC and thermal management, and step-up transformer losses. Round-Trip Efficiency (%) = (Energy Discharged (MWh) ÷ Energy Charged (MWh)) × 100; at 100 MWh charged and 87 MWh discharged, RTE is 87%. Energy Lost per Cycle (MWh) = Energy Charged − Energy Discharged — 13 MWh at the defaults — the energy purchased but never recovered. Cost of Losses per Cycle ($) = Energy Lost per Cycle × Charging Electricity Price ($/MWh); at $30/MWh, that is $390 per cycle. Annual Energy Lost (MWh/year) = Energy Lost per Cycle × Cycles per Year — 13 × 350 = 4,550 MWh/year. Annual Cost of Losses ($/year) = Cost of Losses per Cycle × Cycles per Year — $390 × 350 = $136,500/year. The health flag grades RTE against the typical 85-92% AC range for modern utility-scale lithium-ion BESS: ≥92% excellent, 85-92% healthy, <85% may signal inverter losses, thermal management issues, or degradation. DC-level (cell-only) efficiency is higher (92-98%), but AC system-level efficiency is what matters for revenue and project economics. Data sources: NREL battery storage efficiency studies; utility-scale lithium-ion BESS vendor datasheets (Tesla Megapack, Fluence Gridstack, LG Chem RESU, Saft Intensium Max); IEEE standards for AC/DC efficiency measurement.