Microgrid & Resilience Calculation Methods
Formulas and assumptions behind our microgrid sizing, islanding, backup, and outage cost calculators.
Islanding duration
This calculator estimates the usable energy a battery system can deliver and the resulting islanding duration it can sustain, from the available battery storage capacity, the facility load during islanding, and the battery usable depth of discharge.
Data sources: modern lithium-ion usable depth of discharge of 90-100% from battery manufacturer specifications and NREL energy storage reporting; typical critical load as a fraction of facility peak load from microgrid design guidance and DOE resilience planning resources; islanding duration as usable energy divided by load from standard microgrid and backup power engineering references.
Microgrid sizing
This calculator estimates the total energy a microgrid must deliver during an islanding event and the required battery storage capacity to supply it, from the facility load to support, the desired islanding duration, and the battery round-trip efficiency.
Data sources: critical load as a fraction of facility peak load from microgrid design guidance and DOE resilience planning resources; round-trip efficiency of 85-95% for modern lithium-ion systems from battery manufacturer specifications and NREL energy storage reporting; 2026 microgrid capital costs of roughly $2,500-4,000/kW installed from DOE and NREL microgrid benchmarking.
Microgrid vs. grid-tied cost comparison
This calculator compares the total lifetime cost of building and operating a microgrid against the cost of staying fully grid-tied, from the microgrid capital cost, the annual O&M cost, the annual grid electricity cost without and with the microgrid, and the project life.
Data sources: 2026 microgrid capital costs of roughly $2,500-4,000/kW installed from DOE and NREL microgrid benchmarking; annual O&M commonly estimated at roughly 2% of capital cost from microgrid industry cost reporting; microgrid component design lives of 20+ years from manufacturer specifications and DOE microgrid lifecycle reporting.
Public Safety Power Shutoff (PSPS) outage cost
This calculator estimates the cost of a single Public Safety Power Shutoff event and the total annual PSPS cost a facility faces, from the estimated outage cost rate, the average PSPS event duration, and the number of PSPS events per year.
Data sources: documented ~$500,000 loss from 2019 PSPS events at a California luxury hotel working out to ~$6,799/hour from public PSPS impact reporting and utility resilience filings; typical PSPS event duration of 24-72+ hours from California utility Wildfire Mitigation Plans and CPUC PSPS event reporting; multiple PSPS events per fire season in high-risk utility territories from CPUC and utility PSPS event summaries.
Critical load backup sizing
This calculator sizes a backup system to cover only a facility's critical loads during an outage, from the total critical load, a diversity/simultaneity factor, the required backup duration, the battery round-trip efficiency, and the allowed depth of discharge.
Data sources: diversity factor of 0.7-0.85 for mixed critical loads from microgrid design guidance and NEC load calculation practice; depth-of-discharge limits of 80-100% for modern lithium-ion systems from battery manufacturer specifications and NREL energy storage reporting; round-trip efficiency of 85-95% for modern lithium-ion systems from battery manufacturer specifications and NREL energy storage reporting; 1.25x starting/surge margin convention from standard backup power and generator sizing engineering references.
Microgrid payback period
This calculator estimates the simple payback period of a microgrid investment from the total installed cost, available incentives and rebates, three separate annual savings streams, and the annual O&M cost.
Data sources: demand charges representing 30-70% of commercial electric bills in many utility territories from commercial rate structure analysis and utility tariff reporting; annual O&M commonly estimated at roughly 2% of capital cost from microgrid industry cost reporting; 5-10 year simple payback target band for commercial and industrial microgrids from DOE and NREL microgrid benchmarking.
Resilience value of lost load
This calculator applies the Value of Lost Load (VoLL) framework to a specific facility to estimate the dollar value of the energy an outage would leave unserved, from the facility type, the VoLL rate, the critical load at risk, the expected outage frequency, and the average outage duration.
Data sources: residential VoLL of roughly $5/kWh, commercial VoLL of roughly $20/kWh, industrial VoLL of roughly $35/kWh, and hospital/critical-facility VoLL of roughly $75/kWh from published VoLL studies and DOE/Lawrence Berkeley National Lab interruption cost estimator work; VoLL varying widely by outage duration, time of day, and warning time from the same sources.
Hospital/campus microgrid sizing
This calculator sizes backup generation for a hospital or large campus using the NFPA 110 emergency power system branch concept, from the life safety branch load, the critical/equipment branch load, the optional standby load, a toggle for whether to include standby in sizing, the required runtime, and the backup system type.
Data sources: NFPA 110 emergency power system branch classification and NFPA 99 healthcare facility electrical systems standards; 1.25x starting/inrush margin convention from standard backup power and generator sizing engineering references; typical diesel genset specific fuel consumption of roughly 0.08 gal/kWh from generator manufacturer specifications; 96-hour hospital fuel autonomy benchmark from hospital resilience planning guidance.