Flare Gas-to-Power Calculator

Flaring wastes energy and emits CO2 for nothing. Convert a flare gas volume into on-site power capacity, annual generation, net benefit, simple payback, and the gas diverted from flaring each year.

Associated gas from oil wells is often richer than pipeline gas, around 1,200–1,400 Btu/scf.

Sale price, displaced diesel or grid cost, or the value of power to an on-site load such as a data center or Bitcoin miner.

Flare gas is often free or near-free.

Gas energy
1,200MMBtu/day

volume × 1000 × heating value ÷ 1,000,000

Power capacity
5.26MW

gas energy ÷ 24 ÷ heat rate

Annual generation
42,417MWh

capacity × 8,760 × availability

Annual net benefit
$1,908,758

revenue − O&M − gas cost

Capital cost
$7,894,737

capacity × 1000 × installed cost

Simple payback
4.1years

capital cost ÷ net benefit

Gas diverted from flaring
335.8MMcf/yr

volume × 365 × availability ÷ 1000

Results update live as you type. For planning and field-check estimates — always verify against applicable standards and equipment ratings.

How we calculate this →
Insight

1,000 Mcf per day of flare gas can fuel roughly 5 MW of generation. That is power that can run an on-site data center or Bitcoin mining container instead of venting energy as heat. Economics hinge on gas richness, generator availability and what the electricity is worth on-site. For fuel cost per MWh, see the Heat Rate & Fuel Cost per MWh Calculator; for mining economics, see the ASIC Miner Profitability and Mining Farm Power & Fleet Sizing calculators.

From flare gas to on-site power

Flare gas is natural gas burned off at oil wells or facilities because there is no pipeline or market for it — wasted energy and needless CO2. Converting it to power on-site turns that waste into electricity. The chain starts with gas energy: Gas Energy (MMBtu/day) = flare gas volume (Mcf/day) × 1,000 (scf per Mcf) × heating value (Btu/scf) ÷ 1,000,000. At 1,000 Mcf/day and 1,200 Btu/scf, that is 1,200 MMBtu/day of chemical energy entering the generator.

Power Capacity (MW) = gas energy (MMBtu/day) × 1,000,000 ÷ 24 ÷ heat rate (Btu/kWh) ÷ 1,000 — the 1,000,000 converts MMBtu back to Btu, 24 spreads it across the day, heat rate converts Btu to kWh, and 1,000 converts kW to MW. At 9,500 Btu/kWh, 1,200 MMBtu/day yields about 5.26 MW. Annual generation scales that by 8,760 hours and availability (the share of hours the generator actually runs, typically 90–95% for well-maintained reciprocating engines).

The economics subtract operating costs from revenue: annual revenue = generation × power value, annual O&M = generation × O&M rate, and the gas cost line applies only when the flare gas has a price (it is often free or near-free). Annual net benefit = revenue − O&M − (annual gas used × gas cost). Capital cost = power capacity × 1,000 × installed cost ($/kW), and simple payback = capital cost ÷ annual net benefit. Finally, gas diverted from flaring (MMcf/yr) = flare volume × 365 × availability ÷ 1,000 — the volume no longer burned off. Rich associated gas (1,200–1,400 Btu/scf) carries more energy per cubic foot than pipeline gas (~1,030 Btu/scf), but heavy hydrocarbons and H2S can derate engines and add gas-conditioning cost, which is why cleanup equipment often sits upstream of the generator.

Frequently asked questions

What is flare gas?

Natural gas burned off at oil wells or facilities because there is no pipeline or market for it.

Why use it for power?

It turns wasted gas into electricity on-site, cutting flaring and emissions.

What equipment is used?

Typically gas engines or microturbines, sometimes with gas conditioning.

Do rich gas or impurities matter?

Yes. Heavy hydrocarbons and H2S can derate engines and add cleanup cost.